SEMI-ANNUAL REPORTING FOR CONTINUOUS MONITORING SYSTEMS AND STACK TESTING
MWC UNIT # POLLUTANT OR PARAMETER START DATE TIME OF EXCESS EMISSIONS MONITORED LEVEL APPLICABLE LIMIT SPECIFIC REASON FOR EXCESS CORRECTIVE ACTIONS TAKEN
2 CO 9/18/2007 0400 0759 139 69 SHUTDOWN: leak developed in the superheater section of the unit due to the Turbine Generator being isolated from the power grid. Only 1 hour affected during the 4 hour block Removed MSW from grates as soon as possible to limit emissions.
2 CO 5/7/2007 2000 2359 194 69 SHUTDOWN: to repair tube leak (note that this excess emission was identified during the preparation of year-end reports). Removed MSW from grates as soon as possible to limit emissions.


We hope you find our web site informative. Due to the technical nature of these graphs, we encourage you to call or write us if you have any questions.
Home | Emissions Data Archives | Daily Emissions Data
Site Map


Wheelabrator North Andover
A Waste Management Company
285 Holt Rd.
North Andover, Massachusetts, U.S. 01845
Tel: 978.688.9011

Copyright © Wheelabrator North Andover