SEMI-ANNUAL REPORTING FOR CONTINUOUS MONITORING SYSTEMS AND STACK TESTING
MWC UNIT # POLLUTANT OR PARAMETER START DATE TIME OF EXCESS EMISSIONS MONITORED LEVEL APPLICABLE LIMIT SPECIFIC REASON FOR EXCESS CORRECTIVE ACTIONS TAKEN
1 CO 8/21/2004 20:00 23:59 89 69 Shutdown: superheater tube leak, unable to run gas burners, no water level and zero steam flow. NOTE: excused deviation, less than 3-hours in duration. Follow emergency shutdown procedures
1 CO 11/3/2004 16:00 19:59 205 69 Shutdown: economizer tube leak. NOTE: excused deviation, less than 3-hours in duration. Follow emergency shutdown procedures
2 CO 9/22/2004 08:00 11:59 125 69 Startup following tube leak repair. NOTE: excused deviation, less than 3-hours in duration. Follow normal startup procedures
2 CO 10/21/2004 12:00 15:59 74 69 Startup: following scheduled outage for grate repair. NOTE: excused deviation, less than 3-hours in duration. Follow normal startup procedures
2 CO 11/12/2004 08:00 11:59 142 69 Shutdown: to repair FD Fan bearing. NOTE: excused deviation, less than 3-hours in duration. Follow emergency shutdown procedures