| Plant Name: Wheelabrator North Andover, Inc. |
| Subpart FFF/Cb Annual Report, 40 CFR 39b (a) /40 CFR 60.59b (g) |
| Reporting Period: |
From: 17-Feb-01 |
| |
To: 31-Dec-01 |
| |
| 1. Section 40 CFR 59b(g)(1)(i) - 2 Year Annual PerformanceTest Results |
| |
| |
Current Year |
Previous Year |
Current Year |
Previous Year |
| |
Unit 1 |
Unit 1 |
Unit 2 |
Unit 2 |
| Emission |
Test Result |
Test Result |
Test Result |
Test Result |
| Particulate Matter, mg/dscm @ 7% O2 |
1.4 |
N/A |
1.0 |
N/A |
| Opacity, % |
0 |
N/A |
0 |
N/A |
| Cadmium, mg/dscm @ 7% O2 |
0.00065 |
N/A |
0.00035 |
N/A |
| Lead, mg/dscm @ 7% O2 |
0.0207 |
N/A |
0.0138 |
N/A |
| Mercury, mg/dscm @ 7% O2 |
0.0202 |
N/A |
0.0133 |
N/A |
| Mercury Removal % |
87 |
N/A |
94 |
N/A |
| Dioxins/Furans, ng/dscm @ 7% O2 |
0.6 |
N/A |
0.8 |
N/A |
| Hydrogen Chloride, ppmdv @ 7% O2 |
7.7 |
N/A |
8.0 |
N/A |
| Hydrogen Chloride, % Removal |
99 |
N/A |
99 |
N/A |
| |
| Fugitive Ash, % |
Current Year |
0 |
Previous Year |
N/A |
| |
| 2. Section 40 CFR 60.59b(g)(1)(ii) - Highest Recorded Emission Levels From CEM Data |
| |
| |
Current Year |
Previous Year |
Current Year |
Previous Year |
| Emission or Parameter |
Unit 1 |
Unit 1 |
Unit 2 |
Unit 2 |
Sulfur Dioxide, ppmdv @ 7% O2 (24-hour geometric average) |
25.5 |
N/A |
26.4 |
N/A |
Nitrogen Oxides, ppmdv @ 7% O2 (24-hour arithmetic average) |
204 |
N/A |
210 |
N/A |
Carbon Monoxide, ppmdv @ 7% O2 (4-hour block average) |
469 |
N/A |
392 |
N/A |
Unit Load, lbs/hr steam (4-hour block average) |
170 |
N/A |
171 |
N/A |
Fabric Filter Inlet Temperature, deg F (4-hour block average) |
331 |
N/A |
329 |
N/A |
| |
| Plant Name: Wheelabrator North Andover, Inc. |
| Subpart FFF/Cb Annual Report, 40 CFR 39b (a) /40 CFR 60.59b (g) |
| Reporting Period: |
From: 17-Feb-01 |
| |
To: 31-Dec-01 |
| |
| 3. Section 40 CFR 60.59b(g)(1)(iii) - Highest Measured Opacity Level |
| |
| |
Current Year |
Previous Year |
Current Year |
Previous Year |
| Emission |
Test Result |
Test Result |
Test Result |
Test Result |
Opacity, % (6-minute block average) |
3.5 |
N/A |
9.0 |
N/A |
| |
| 4. Section 40 CFR 60.59b(g)(1)(iv) -Total Days CEMS Did Not Obtain Valid Data for 75% of Boiler Operating Time |
| |
| |
Current Year |
Previous Year |
Current Year |
Previous Year |
| Continuous Emission Monitor |
Unit 1 |
Unit 1 |
Unit 2 |
Unit 2 |
| Sulfur Dioxide, ppmdv @ 7% O2 |
6 |
N/A |
3 |
N/A |
| Nitrogen Oxides, ppmdv @ 7% O2 |
5 |
N/A |
3 |
N/A |
| Carbon Monoxide, ppmdv @ 7% O2 |
3 |
N/A |
1 |
N/A |
| Unit Load, lbs/hr steam |
0 |
N/A |
0 |
N/A |
| Fabric Filter Inlet Temperature, deg F |
0 |
N/A |
0 |
N/A |
| |
| 5. Section 40 CFR 60.59b(g)(1)(v) - Total Number of Hours CEMS Data Was Excluded From Calculations |
| |
| |
Current Year |
Previous Year |
Current Year |
Previous Year |
| Emission or Parameter |
Unit 1 |
Unit 1 |
Unit 2 |
Unit 2 |
| Sulfur Dioxide, ppmdv @ 7% O2 |
105 |
N/A |
68 |
N/A |
| Nitrogen Oxides, ppmdv @ 7% O2 |
80 |
N/A |
65 |
N/A |
| Carbon Monoxide, ppmdv @ 7% O2 |
55 |
N/A |
40 |
N/A |
| Unit Load, lbs/hr steam |
0 |
N/A |
0 |
N/A |
| Fabric Filter Inlet Temperature, deg F |
0 |
N/A |
0 |
N/A |
| Plant Name: Wheelabrator North Andover, Inc. |
| Subpart FFF/Cb Annual Report, 40 CFR 39b (a) /40 CFR 60.59b (g) |
| Reporting Period: |
From: 17-Feb-01 |
| |
To: 31-Dec-01 |
| |
| 6. Section 40 CFR 60.59b(g)(3) - Highlight of Emission or Parameter That Did Not Achieve Emission Limit |
| |
| Emission or Parameter |
Unit # |
Date |
Magnitude |
Explanation Summary |
| Carbon Monoxide |
1 |
4/8/01 |
469 |
shutdown - planned maintenance |
| Nitrogen Oxides |
2 |
4/16/01 |
210 |
malfunction - urea pumps tripped |
| Carbon Monoxide |
2 |
12/5/01 |
392 |
shutdown - tube repair |
|
|
 |
|