Plant Name: Wheelabrator North Andover, Inc.
Subpart FFF/Cb Annual Report, 40 CFR 39b (a) /40 CFR 60.59b (g)
Reporting Period: From: 17-Feb-01
  To: 31-Dec-01
 
1. Section 40 CFR 59b(g)(1)(i) - 2 Year Annual PerformanceTest Results
 
  Current Year Previous Year Current Year Previous Year
  Unit 1 Unit 1 Unit 2 Unit 2
Emission Test Result Test Result Test Result Test Result
Particulate Matter, mg/dscm @ 7% O2 1.4 N/A 1.0 N/A
Opacity, % 0 N/A 0 N/A
Cadmium, mg/dscm @ 7% O2 0.00065 N/A 0.00035 N/A
Lead, mg/dscm @ 7% O2 0.0207 N/A 0.0138 N/A
Mercury, mg/dscm @ 7% O2 0.0202 N/A 0.0133 N/A
Mercury Removal % 87 N/A 94 N/A
Dioxins/Furans, ng/dscm @ 7% O2 0.6 N/A 0.8 N/A
Hydrogen Chloride, ppmdv @ 7% O2 7.7 N/A 8.0 N/A
Hydrogen Chloride, % Removal 99 N/A 99 N/A
 
Fugitive Ash, % Current Year 0 Previous Year N/A
 
2. Section 40 CFR 60.59b(g)(1)(ii) - Highest Recorded Emission Levels From CEM Data
 
  Current Year Previous Year Current Year Previous Year
Emission or Parameter Unit 1 Unit 1 Unit 2 Unit 2
Sulfur Dioxide, ppmdv @ 7% O2
(24-hour geometric average)
25.5 N/A 26.4 N/A
Nitrogen Oxides, ppmdv @ 7% O2
(24-hour arithmetic average)
204 N/A 210 N/A
Carbon Monoxide, ppmdv @ 7% O2
(4-hour block average)
469 N/A 392 N/A
Unit Load, lbs/hr steam
(4-hour block average)
170 N/A 171 N/A
Fabric Filter Inlet Temperature, deg F
(4-hour block average)
331 N/A 329 N/A
 


Plant Name: Wheelabrator North Andover, Inc.
Subpart FFF/Cb Annual Report, 40 CFR 39b (a) /40 CFR 60.59b (g)
Reporting Period: From: 17-Feb-01
  To: 31-Dec-01
 
3. Section 40 CFR 60.59b(g)(1)(iii) - Highest Measured Opacity Level
 
  Current Year Previous Year Current Year Previous Year
Emission Test Result Test Result Test Result Test Result
Opacity, %
(6-minute block average)
3.5 N/A 9.0 N/A
 
4. Section 40 CFR 60.59b(g)(1)(iv) -Total Days CEMS Did Not Obtain Valid Data for 75% of Boiler Operating Time
 
  Current Year Previous Year Current Year Previous Year
Continuous Emission Monitor Unit 1 Unit 1 Unit 2 Unit 2
Sulfur Dioxide, ppmdv @ 7% O2 6 N/A 3 N/A
Nitrogen Oxides, ppmdv @ 7% O2 5 N/A 3 N/A
Carbon Monoxide, ppmdv @ 7% O2 3 N/A 1 N/A
Unit Load, lbs/hr steam 0 N/A 0 N/A
Fabric Filter Inlet Temperature, deg F 0 N/A 0 N/A
 
5. Section 40 CFR 60.59b(g)(1)(v) - Total Number of Hours CEMS Data Was Excluded From Calculations
 
  Current Year Previous Year Current Year Previous Year
Emission or Parameter Unit 1 Unit 1 Unit 2 Unit 2
Sulfur Dioxide, ppmdv @ 7% O2 105 N/A 68 N/A
Nitrogen Oxides, ppmdv @ 7% O2 80 N/A 65 N/A
Carbon Monoxide, ppmdv @ 7% O2 55 N/A 40 N/A
Unit Load, lbs/hr steam 0 N/A 0 N/A
Fabric Filter Inlet Temperature, deg F 0 N/A 0 N/A


Plant Name: Wheelabrator North Andover, Inc.
Subpart FFF/Cb Annual Report, 40 CFR 39b (a) /40 CFR 60.59b (g)
Reporting Period: From: 17-Feb-01
  To: 31-Dec-01
 
6. Section 40 CFR 60.59b(g)(3) - Highlight of Emission or Parameter That Did Not Achieve Emission Limit
 
Emission or Parameter Unit # Date Magnitude Explanation Summary
Carbon Monoxide 1 4/8/01 469 shutdown - planned maintenance
Nitrogen Oxides 2 4/16/01 210 malfunction - urea pumps tripped
Carbon Monoxide 2 12/5/01 392 shutdown - tube repair


We hope you find our web site informative. Due to the technical nature of these graphs, we encourage you to call or write us if you have any questions.
Home | Emissions Data Archives | Daily Emissions Data
Site Map


Wheelabrator North Andover
A Waste Management Company
285 Holt Rd.
North Andover, Massachusetts, U.S. 01845
Tel: 978.688.9011